Oil and Chemical Plant Layout and Spacing
GE GAP Guidelines
A Publication of GE Global Asset Protection Services

GAP.2.5.2 September 3, 2001

OIL AND CHEMICAL PLANT LAYOUT AND SPACING
INTRODUCTION
Loss experience clearly shows that fires or explosions in congested areas of oil and chemical plants can result in extensive losses. Wherever explosion or fire hazards exist, proper plant layout and adequate spacing between hazards are essential to loss prevention and control. Layout relates to the relative position of equipment or units within a given site. Spacing pertains to minimum distances between units or equipment. GE Global Asset Protection Services (GE GAP Services) layout and spacing recommendations are for property loss prevention purposes only and are intended for existing and new oil and chemical facilities. These guidelines are intended to limit explosion overpressure and fire exposure damage. They do not address shrapnel damage. If these guidelines cannot be followed, then additional loss control measures, such as fire proofing, waterspray or blast hardening will be necessary. GE GAP Services guidelines only address spacing and layout within a plant and are mostly applicable to open structures. An open air design favors vapor dissipation, provides adequate ventilation, reduces the size of the electrically classified area, and increases firefighting accessibility. Additional information can be found in several publications.1

POSITION Management Programs
Management program administrators should report to top management through the minimum number of steps. They should also institute loss prevention inspection and audit programs to communicate program effectiveness to top management. This management feedback is a key feature of GAP.1.0.1 (OVERVIEW).2 In developing a program, pay particular attention to the following important areas: Hazard Identification and Evaluation Program Determine the plant layout and spacing necessary to limit loss size based on worst case scenarios for vapor cloud,



References: 1. Hazard Survey of the Chemical and Allied Industries, Technical Survey No. 3, 1968, American Insurance Association, New York, NY. An Engineer’s Guide To Process-Plant Layout, F.F. House, July 28, 1969, Chemical Engineering, McGraw Hill, New York, NY. Process Plant Layout, by J.C. Mecklenburgh, John Wiley & Sons, New York, NY. Loss Prevention In The Process Industries, F. P. Lees, Volumes 1 & 2, Butterworths, Boston, MA. Loss Prevention Fundamentals For The Process Industry, O. M. Slye Jr., Loss Prevention Symposium, March 1988, American Institute of Chemical Engineers, New York, NY. NFPA 30-2000, Flammable And Combustible Liquids Code, National Fire Protection Association, Quincy, MA. NFPA 58-2001, Liquefied Natural Gas, National Fire Protection Association, Quincy, MA. 2. 3. 4. 5. 6. 7. OVERVIEW, GE Global Asset Protection Services. NFPA 496-1998, Purged And Pressurized Enclosures For Electrical Equipment In Hazardous (Classified) Locations, National Fire Protection Association, Quincy, MA. API RP 521-1982: Guide For Pressure-Relieving And Depressurizing Systems, American Petroleum Institute, Washington, DC. Center for Chemical Process Safety, American Institute of Chemical Engineers, New York, NY. Fire & Explosion Index, Hazard Classification Guide, Dow Chemical Company, Sixth edition, available from the American Institute of Chemical Engineers, New York, NY. API RP 752-1995: Management of Hazards Associated with Location of Process Plant Buildings, American Petroleum Institute, Washington, DC. GE GAP Guidelines 13 A Publication of GE Global Asset Protection Services

You May Also Find These Documents Helpful

  • Good Essays

    Cited: Arnold, J. “Large Building Fires and Subsequent Code Changes.”NFPA.ORG. CCFD. 7 April 2005. Web. 24 March 2011.…

    • 809 Words
    • 4 Pages
    Good Essays
  • Good Essays

    Cdl Review

    • 630 Words
    • 3 Pages

    A guidebook for firefighters, police, and industry workers on how to protect themselves and the public from hazardous materials.…

    • 630 Words
    • 3 Pages
    Good Essays
  • Best Essays

    Cocoanut Grove Case

    • 2606 Words
    • 11 Pages

    outside the theater district on the edge of Bay Village, one of the city’s oldest historical…

    • 2606 Words
    • 11 Pages
    Best Essays
  • Better Essays

    Gulf Refinery Fire

    • 1382 Words
    • 6 Pages

    In the early hours of August 17, 1975, a tragic disaster occurred on the Gulf Oil refinery in Philadelphia, Pennsylvania. This horrific disaster took the lives of eight firefighters, and potentially could have taken more lives if it wasn’t for the help of many surrounding fire stations. The cause of the fire was the overfilling of Tank 231. While no crude oil escaped from the tank as a result of being overfilled, large quantities of hydrocarbon vapors were trapped above the surface of the tank’s crude oil. As the quantity of crude oil increased, these hydrocarbon vapors were forced out of the tank’s vents and into the area of the No.4 Boiler House where the initial flash occurred. The overfilling of the tank resulted from a failure of the tanker’s personnel to properly monitor the quantity of crude oil being pumped to the tank. This whole disaster could have been avoided by just double checking the amount of crude oil in Tank 231.…

    • 1382 Words
    • 6 Pages
    Better Essays
  • Satisfactory Essays

    Unit 4 Ip

    • 537 Words
    • 3 Pages

    References: Power Plant Pollution Control. (n.d.). Engineering Services Outsourcing. Retrieved February 4, 2013, from http://www.engineeringservicesoutsourcing…

    • 537 Words
    • 3 Pages
    Satisfactory Essays
  • Satisfactory Essays

    course notes

    • 1310 Words
    • 6 Pages

    Note both controlled and uncontrolled fire hazards (sources of ignition, fuel and oxygen), risks of fire spread (fire protection measures) and risk to persons (emergency evacuation measures and procedures) Note measures in place to reduce the risk of fire occurring, to reduce the risk of fire spread and measures and procedures to remove / reduce the risk to persons from fire Chip pan Cooker Grill Smoking Toasters Lamps Electric fires Chip pan used infrequently Paint Thinners Oils Petrol…

    • 1310 Words
    • 6 Pages
    Satisfactory Essays
  • Good Essays

    The global fire protection community should incorporate wet chemical extinguishing systems as part of its essential technique in firefighting. Wet chemical extinguishing can be instrumental in combating the risk fires would have on employees and equipment in the workplace (Jones, 2009). It works by cooling and timely response would ensure that individuals are not affected adversely by heat during a fire out-break. There has been an increase in the improvement of cooking appliances, heating rates and industrial tendency to unsaturated oil. These are potential conditions for severe fires and wet chemical extinguishing would come in handy in mitigating such possibilities.…

    • 314 Words
    • 2 Pages
    Good Essays
  • Good Essays

    Firefighter Safety

    • 849 Words
    • 4 Pages

    There is also a risk to flow water on the energized systems. Avoid direct hose streams on the system. A 100 psi is needed at the nozzle. A fog spray should be set to a 30 degree fog pattern at 100 psi and the firefighters should hit the fire from at least 33 ft away from the energized source. Straight streams and foam should not be used due to being a great conductor for energy. Also be aware of run off which may run into those PV systems that are on the ground. Overhaul should be done when the system has been totally de-engergized due to the hidden hazards that are hiding in the walls. A risk verses benefit may need to be taken in consideration with PV systems. If the PV system is the source of the fire than fire strategy should be to protect exposers. Any tools that are used during operations should be non-conductive tools.…

    • 849 Words
    • 4 Pages
    Good Essays
  • Better Essays

    Kulkarini, H. K., R. Bhattacharya. (2011). A look at disaster management strategies for chemical industries. Retrieved from http://www.process-worldwide.com/explosion_protection_safety_security/plant_protection/safety_engineering/articles/316211/index3.html…

    • 1856 Words
    • 8 Pages
    Better Essays
  • Good Essays

    On the 28th of February 2008, a leak of extremely flammable hydrocarbon an explosion had a taken place at the bacton gas terminal in Norfolk, located in the north east of England. This lead to a large amount of concrete and metal coming from the roof being propelled 100 meters high, alongside a huge fire that took 50 firefighters two hours to put out. Fortunately all 46 personnel were evacuated from the site unhurt. That was down to good fortune due the fact that it occurred during a shift change. Becton gas terminal consists of 5 gas terminals known as Interconnector, Eni, Perenco, Shell and national grid. The gas terminals are owned by Royal Dutch shell, ExxonMobil and Perenco receiving gas from…

    • 719 Words
    • 3 Pages
    Good Essays
  • Better Essays

    Hazmat

    • 1077 Words
    • 5 Pages

    The basic incident command system works from the 3 principles of life safety, property conservation, and incident stabilization. With life safety being performed with the removal of the workers near the spill and receiving medical attention I can now turn my attention to the materials involved. I would consider sheltering in place all of the plant except the production area. This area would need to be evacuated as soon as possible due to the area being next to the spill. With the product staring to off gas I need to shut down any air handlers in that area to prevent the gas from traveling though out the building or the site and causing more harm to the workers. I know that I have oxidizers, flammable, acids, and bases stored in the same area but in different bins. I also know that acids and bases are chemical opposites that react violently with each other, often producing heat, explosions or toxic gases. Since they are powerful corrosives, they can react with many other substances. Many acids are also oxidizers and can create fires if they react with combustible materials.…

    • 1077 Words
    • 5 Pages
    Better Essays
  • Good Essays

    DBD and NBD indicate the risk of property damage because of fire or explosion. Equation 32 is proposed for DBD score. If 308 this distance is greater than 1000 m, then DBD = 0. If the distance…

    • 1766 Words
    • 8 Pages
    Good Essays
  • Satisfactory Essays

    Plant Layout Optimization

    • 3009 Words
    • 13 Pages

    The optimum sequence method starts with an arbitrary initial solution and tries to improve the layout by switching two departments in the sequence. At each step the method computes the cost changes for all possible switches of two departments and chooses the most effective pair. The two departments are switched in sequence and the method repeats. The process stops when no switch results in a reduced cost. The optimized facility information and layout have been shown below.…

    • 3009 Words
    • 13 Pages
    Satisfactory Essays
  • Powerful Essays

    1. Prescriptive requirements are developed for general use but not for specific purposes. Under certain circumstances, engineering methods can be used to justify certain alternative approaches to resolve fire safety problems. This will motivate designers of building such as architect and engineers to be creative and innovative. This basic framework is developed in order to guide and assist the stakeholders of the building if they intend to adopt performancebased approaches. The International Fire Engineering Guidelines (IFEG) shall be used to facilitate the development of performance-based solutions for the building. IFEG have been developed to meet the joint needs in U.S.A, Canada, New Zealand and Australia. This guidebook references internationally available standards, guides and associated documents, and use both imperial and SI units throughout. In particular, the guidelines provide guidance for the design and evaluation of alternative solutions (equivalencies) and general performance design. The International Fire Engineering Guidelines (IFEG) have been developed: a. To be used in fire engineering design and evaluation of buildings. However, the concepts and principles may also be of assistance in a fire engineering evaluation of other structures such as ships and tunnels that are comprised of enclosed spaces. b. To provide guidance for fire engineers to design and evaluate fire safety systems to achieve acceptable levels of safety. c. To assume the fire engineer has a level of competence and experience that would enable licensing by the respective nation. The submission of alternative solution to prescriptive requirement shall be at least in two stages: a. Fire Engineering Brief and b. Fire Engineering Final Report The International Fire Engineering Guidelines (IFEG) provides the details of…

    • 6780 Words
    • 28 Pages
    Powerful Essays
  • Satisfactory Essays

    Fire Insurance in India.

    • 405 Words
    • 2 Pages

    Standard Fire and Special Perils Policy covers 12 perils. FIRE, LIGHTENING, EXPLOSION/IMPLOSION, AIRCRAFT DAMAGE, STORM & ALLIED PERILS, IMPACT DAMAGE, SUBSIDENCE AND LANDLISED INCLUDING ROCK SLIDE, BURSTING AND/OR OVERFLOWING OF WATER TANKS APPARATUS AND PIPES, MISSILE TESTING OPERATIONS, LEAKAGE OF AUTMATIC SPRINKLER INSTALLATIONS, BUSH FIRE…

    • 405 Words
    • 2 Pages
    Satisfactory Essays