Control of an Electronic Expansion Valve Using an Adaptive Pid Controller
2387, Page 1
Control of an Electronic Expansion Valve Using an Adaptive PID Controller
Antônio A. T. Maia*, Marconi A. Silva, Ricardo N. N. Koury, Luiz Machado, Alexandre C. Eduardo
Federal University of Minas Gerais, Mechanical Engineering Department,
Belo Horizonte, Minas Gerais, Brazil
Phone: + (55 31) 3409 6667, Fax: + (55 31) 3443 3783, e-mail: aamaia@ufmg.br

ABSTRACT
In many refrigeration systems, electronic expansion devices have been used to replace the conventional expansion devices like capillary tubes and thermostatic expansion valves. The electronic expansion devices are usually provided with an automatic controller that is responsible for determining the valve opening that keeps the superheat at the outlet of the evaporator within the desired limits. Most of these controllers permit only the adjustment of the desired superheat, the proportional, the integral and the derivative gains. After being adjusted for one operating point, these parameters do not suffer any automatic correction even when the operating conditions changes. This could penalize the system efficiency because the controller parameters defined initially may not be the most suitable for the system when operating in this new condition. Within this context, in this work it was developed an adaptive
PID-controller to regulate the superheat degree at the outlet of the evaporator. A dynamic model obtained from experimental tests was used in the controller design. The controller effectiveness was evaluated by means of computer simulation and through experimental tests. The results obtained showed that the employed technique is effective in regulating the superheat degree at the outlet of the evaporator with an acceptable performance.

1. INTRODUCTION
The increase in the energy prices in the last decades has motivated many research works to identify great energy consumers and ways to improve the efficiency of these systems. In this context, refrigerating machines have a



References: Åström, K. J. and Wittenmark, B., 1995, Adaptive control, Massachussetts, Addison-Wesley, 2ª ed. 574p. Chen, W., Zhijiu, C., Ruiqi, Z., Yezheng, W., 2002, Experimental investigation of a minimum stable superheat control system of an evaporator Cominos, P. and Munro, N., 2002, PID controllers: recent tuning methods and design to specification. IEE Proc. Ekren, O. and Küçüca, S., 2009, Energy saving potential of a chiller system with fuzzy logic control, International Journal Of Energy Research. Fallahsohi, H., Changenet, C., Placé, S., Ligeret, C., Lin-Shi, X., 2010, Predictive functional control of an expansion valve for minimizing the superheat of an evaporator Lazzarin, R. and Noro, M., 2008, Experimental comparison of electronic and thermostatic expansion valves performances in an air conditioning plant, International Journal of Refrigeration, V Maia, Antônio A. T., 2005, Metodologia de desenvolvimento de um algoritmo para controle simultâneo da capacidade de refrigeração e do grau de superaquecimento de um sistema de refrigeração, Tese (Doutorado), Microchip, 2003, PIC16F87XA data sheet, Microchip Technology Inc., USA, 232 p. National, 2001, PID control tool set user manual, National Instruments Corporation, USA, 180 pp. Ogata, K., 2003, Engenharia de controle moderno, Prentice Hall, São Paulo, Brazil, 4ª ed., 788p. Outtagarts, A., Haberschill, P., Lallemand, M. 1997, The transient response of an evaporator fed through an electronic expansion valve Vilanova, R., 2008, IMC based Robust PID design: Tuning guidelines and automatic tuning. Journal of Process Control, Vol International Refrigeration and Air Conditioning Conference at Purdue, July 12-15, 2010

You May Also Find These Documents Helpful

  • Good Essays

    Mae219 Unit 9 Study Guide

    • 613 Words
    • 3 Pages

    Air in an ideal Diesel cycle is compressed from 4 L to 0.25 L, and then it expands during the constant pressure heat addition process to 0.50 L. Under cold air standard conditions, determine the thermal efficiency of this cycle.…

    • 613 Words
    • 3 Pages
    Good Essays
  • Powerful Essays

    Nt1330 Unit 5 Lab Report

    • 1050 Words
    • 5 Pages

    To explore the effectiveness of the proposed techniques, computer simulation has been carried out. The conventional PID, GA-PID and ACO-PID controllers were simulated using Matlab-Simulink software on a PC. In the simulation software package, operation of the entire system [i.e. the working of the voltage source inverter, switches operation, position of the rotor, reference and actual speed values, speed error and change in the error] can be observed.…

    • 1050 Words
    • 5 Pages
    Powerful Essays
  • Good Essays

    3) (2 point) Which of the four common control objectives is most enhanced by this control feature in this situation? Explain.…

    • 711 Words
    • 3 Pages
    Good Essays
  • Good Essays

    In the appendix, show the derivation to obtain the equation used to calculate the heat capacity of the calorimeter.…

    • 2516 Words
    • 11 Pages
    Good Essays
  • Powerful Essays

    For heat pumps, in order to achieve the Energy Star, it must be able to perform efficiently at 2…

    • 1241 Words
    • 5 Pages
    Powerful Essays
  • Good Essays

    Txv Information

    • 830 Words
    • 4 Pages

    The thermostatic expansion valve, TEV, controls the flow of liquid refrigerant entering the direct expansion, DX, evaporator by maintaining a constant superheat of the refrigerant vapor at the outlet of the evaporator. Superheat is the difference between the refrigerant vapor temperature and its saturation temperature. To measure the superheat is the difference between the actual temperature at the sensing bulb or near the compressor and the saturation temperature corresponding to the suction pressure.…

    • 830 Words
    • 4 Pages
    Good Essays
  • Satisfactory Essays

    Rize Documentary

    • 528 Words
    • 3 Pages

    This provides the motivation for operational control frameworks with an expanded set of performance measures:…

    • 528 Words
    • 3 Pages
    Satisfactory Essays
  • Good Essays

    Hvac

    • 673 Words
    • 3 Pages

    Shell and tube water cooled condensers Vertical shell and tube condensers Surface condenser Counter flow in condensers Cross flow in condensers Air cooled condensers Cooling Tower…

    • 673 Words
    • 3 Pages
    Good Essays
  • Good Essays

    Acl Chapter 9

    • 517 Words
    • 3 Pages

    Based on the results from the operations you completed above, can the control be considered effective? Why or why not?…

    • 517 Words
    • 3 Pages
    Good Essays
  • Good Essays

    For the heat rates given in the previous question, the hot water temperature decreases from 65.1…

    • 505 Words
    • 3 Pages
    Good Essays
  • Satisfactory Essays

    Hvac

    • 787 Words
    • 4 Pages

    There is also a liquid force from the liquid line, which acts on the face of the needle valve and has a tendency to open the valve. However, this force is cancelled out when using a balanced port TXV. Working together, these forces maintain a constant evaporator superheat in a refrigeration system. There are no electronic devices associated with a conventional TXV.…

    • 787 Words
    • 4 Pages
    Satisfactory Essays
  • Good Essays

    The Loverboy

    • 1221 Words
    • 5 Pages

    Further refinements like PID control would help compensate for additional variables like hills, where the amount of power needed for a given speed change would vary, which would be…

    • 1221 Words
    • 5 Pages
    Good Essays
  • Good Essays

    Thermos lab

    • 2047 Words
    • 9 Pages

    OBJECTIVE—of this exercise is to determine the various coefficients of performance, COP. Specifically, these are the ideal and actual cycle COPs using the attached thermodynamic diagram for Refrigerant-12 (R12).…

    • 2047 Words
    • 9 Pages
    Good Essays
  • Good Essays

    REFRIGERATION SYSTEM COMPONENTS There are five basic components of a refrigeration system, these are: Evaporator Compressor Condenser Expansion Valve Refrigerant; to conduct the heat from the product In order for the refrigeration cycle to operate successfully each component must be present within the refrigeration system. The Evaporator The purpose of the evaporator is to remove unwanted heat from the product, via the liquid refrigerant. The liquid refrigerant contained within the evaporator is boiling at a low-pressure. The level of this pressure is determined by two factors: The rate at which the heat is absorbed from the product to the liquid refrigerant in the evaporator The rate at which the low-pressure vapour is removed from the evaporator by the compressor To enable the transfer of heat, the temperature of the liquid refrigerant must be lower than the temperature of the product being cooled. Once transferred, the liquid refrigerant is drawn from the evaporator by the compressor via the suction line. When leaving the evaporator coil the liquid refrigerant is in vapour form. The Compressor The purpose of the compressor is to draw the low-temperature, low-pressure vapour from the evaporator via the suction line. Once drawn, the vapour is compressed. When vapour is compressed it rises in temperature. Therefore, the compressor transforms the vapour from a low-temperature vapour to a high-temperature vapour, in turn increasing the pressure. The vapour is then…

    • 930 Words
    • 4 Pages
    Good Essays
  • Best Essays

    ---. "An Introduction to System Design and Control". Bronx NY, 2008. Lecture Note. SUNY Maritime College. July 8, 2008.…

    • 4987 Words
    • 143 Pages
    Best Essays